Laserfiche WebLink
TABLE 7.1.2-2 <br />Wastewater Conv.eyance System Design Criteria - Existing and 2025 Capacity Needs <br />MWMC Facilities Plan, Eugene-Springfield <br /> <br /> Unit Process Existing Criteria/Conditions Year 2025 <br /> <br /> Horsepower 2 @ 20 hp 2 @ 30 hp <br /> Drive on/off on/off <br /> Capacity <br /> Total 1.4 mgd 2.0 mgd <br />Firm (largest unit out) 0.7 mgd 1.0 mgd <br />Skipper Pump Station <br />Pumps <br />Number of Pumps 2 3 <br />Size 2 @ 3 mgd 3 @ 3.5 mgd <br />Type Dry pit centrifugal Dry pit centrifugal <br />Horsepower 2 @ 60 hp 3 @ 100 hp <br />Drive on/off on/off <br />Capacity <br />Total 6.0 mgd 10.5 mgd <br />Firm (largest unit out) 3.0 mgd 7.0 mgd <br />Greenwich Pump Station <br />Pumps <br />Number of Pumps 2 2 <br />Size 2 @ 0.7 mgd 2 @ 1.5 mgd <br />Type Dry pit centrifugal Dry pit centrifugal <br />Horsepower 2 @ 30 hp 2 @ 30 hp <br />Drive on/off on/off <br />Capacity <br />Total 2.1 mgd 3.0 mgd <br />Firm (largest unit out) 1.0 mgd 1.5 mgd <br />Irvington Pump Station <br />Pumps <br />Number of Pumps 2 3 <br />Size 2 @ 7.2 mgd 3 @ 5 mgd <br />Type Dry pit centrifugal Dry pit centrifugal <br />Horsepower 2 @ 150 hp 3 @ 250 mgd <br />Drive VFD VFD <br />Capacity <br />Total 13.5 mgd 15.0 mgd <br />Firm (largest unit out) 7.2 mgd 10.0 mgd <br />West Irwin Pump Station <br />Pumps <br />Number of Pumps 3 3 <br />Size 3 @ 9 mgd 3 @ 9.5 mgd <br />Type Dry pit centrifugal Dry pit centrifugal <br />Horsepower 2 @ 200 hp 3 @ 250 hp <br /> I @ 250 hp <br /> <br />MWMC_TABLE 7.1.2*2_REV4.DOC 2 <br /> <br /> <br />