Laserfiche WebLink
MWMCF~IL1TIESP~N <br /> <br />TABLE 5.1.1-1 <br />Existing NPDES Discharge Requirements and Limitations for the WPCF <br />MWMC Facilities Plan, Eugene-Springfield <br /> <br /> CBODs and TSS Removal Shall not be less than 85% monthly average for CBOD5 and <br /> Efficiency 85% monthly for TSS. <br /> <br /> Total Residual Chlorine Shall not exceed a monthly average concentration of 0.05 mg/L <br /> or a daily average concentration of 0.12 mg/L <br /> <br /> Excess Thermal Loading: May Shall not exceed a weekly average of 3.1 billion BTUs per day <br /> 1 - Oct 31 (Summer) <br /> <br /> Ammonia: May 1 - Oct 31 Shall not exceed 22 mg/L daily <br /> (Summer) <br /> Ma~Jmum and 12 mgJL monthly average, <br /> <br /> (Not speclhed in permit, but should be expressed as <br /> Ammonia-N) <br /> <br />(1) The permit also defines the m~xing zone as follows: <br /> <br />The allowable mixing zone is that portion of the Willamette River from 20 feet upstream of the diffuser to 200 feet <br />downstream of the diffuser. In addition, the zone of immediate dilution (ZID) shall include that portion of the <br />Willamette River within 50 feet downstream of the diffuser. <br /> <br />(1) The permit also contains the following language regarding effluent limitations: <br /> <br />This permit contains either technology or water quality based effluent limits for those parameters discharged by <br />the perm~ttee that the Department has determined require effluent limitations to comply with the water quality <br />standards found in OAR 340-41-445 outside the above mixing zones. The limits were established on the basis of <br />the information provided by the permittee and following the Department's rules, including OAR 340-41-026. <br />Other parameters also were identified m the perm/tree's application for which the Department did not establish <br />effluent limitations. The Department has determined that those parameters do not present a reasonable potential <br />to violate applicable water quality standards. The perm/tree is required to notify the Department if changes occur <br />in Its processes or influent stream which could significantly change the effluent stream for any of these <br />parameters. <br /> <br />(2) Reclaimed wastewater outfal1101 and 102 <br /> <br /> No d~scharge to state waters is permitted. Alt reclaimed water reuse shall prevent: <br /> <br /> a. Prolonged pending of treated reclaimed water on the ground surface <br /> b. Surface runoff or subsurface drainage through drainage tile <br /> The creation of odors, fly and mosqu~to breeding, or other nuisance conditions <br /> d. The overloading of land w~th nutrients, organics, or other pollutar~t parameters <br /> e. Impairment of existing or reasonably probable beneficial uses of groundwater <br /> <br /> Out/all 101: <br /> <br /> Pdor to reuse of the reclaimed water, it shall receive at least Level ii treatment as defined in <br /> OAR 340-55 to: Reduce total coliform to 240 organisms per 100 mL in two consecutive samples, <br /> and a 7-day median of 23 organisms per 100 mL. <br /> <br /> Outfal~ 102: <br /> <br /> Prior to reuse of the reclaimed water, it shall receive at least Level iii treatment as defined in <br /> OAR 340-55 to: Reduce total coliform to 7-day median of 2.2 organisms per 100 mL and maximum <br /> of 23 organisms per 100 mL. <br /> <br /> irrigation shall conform to the irrigation management p/an approved by the Department ~n <br /> accordance w~th OAR 340-55 for agricultural, commemial, or industrial use. <br /> <br />(3) Emergency Overflow Outfalls 002 through 014 <br /> <br /> <br />