HomeMy WebLinkAboutAdmin Order 52-26-02 -- Proposing Fire Code AmendmentsAdministrative Order - Page 1 of 17 ADMINISTRATIVE ORDER NO. 52-26-02 of the City Manager of the City of Eugene REGARDING THE OPPORTUNITY TO COMMENT ON A PROPOSAL TO AMEND EUGENE FIRE CODE ADMINISTRATIVE RULE R-8.010FC. The City Manager of the City of Eugene finds that: A.Section 8.010 of the Eugene Code, 1971 (EC), authorizes the City Manager to administratively adopt a fire code for the City of Eugene. Pursuant to that authority, and in accordance with the procedures set forth in EC 2.019, on August 10, 2023, Administrative Order 52-23-02-F was issued adopting Eugene Fire Code Administrative Rule R-8.010FC. B.It is necessary to amend Eugene Fire Code Administrative Rule R-8.010FC so that the City’s Fire Code will be consistent with the 2025 Oregon Fire Code, and to maintain a reasonable degree of fire and life safety for the community at large. THEREFORE, I propose that Eugene Fire Code Administrative Rule R-8.010FC be amended as set forth below, and I order that a Notice of the intended Rule amendments substantially conforming to the Notice attached as Exhibit A to this Order, shall be: 1.Made available to any person who has requested such notice; 2.Made available to any business which possesses a license issued pursuant to this Rule; 3.Provided to the City Council and, to the extent required by state law, to the state and Lane County; and 4.Published in the Register Guard Newspaper for at least five days. PROPOSED AMENDMENTS TO EUGENE FIRE CODE ADMINISTRATIVE RULE R-8.010FC R-8.0lOFC-A ADOPTION. The 2024 International Fire Code (IFC) as promulgated by the International Code Council, and as adopted and amended by the State of Oregon as the 2025 Oregon Fire Code (OFC), as authorized by ORS 476.030 and OAR 837, Division 40, and effective October 1, 2025, is hereby Administrative Order - Page 2 of 17 adopted, subject to the additions, deletions, and modifications set forth in Section R-8.010FC-B of this rule, which together constitute the Eugene Fire Code (“EFC” or “this code”). This rule is in addition to, and is not exclusive of, Administrative Rule R-8.005. R-8.0lOFC-B AMENDMENTS. 1. Section 101.1 of the OFC is amended to provide: 101.1 Title. These regulations shall be known as the Eugene Fire Code (EFC), hereinafter referred to as “this code.” 2. Section 101.2.1 of the OFC is amended to provide: 101.2.1 Appendices. Provisions in the appendices shall not apply unless specifically adopted. The provisions of the following appendices are adopted as part of this code: B, C, D, E, G, H, I, L, N and O. 3. The following Section 102.3.1 is added to the OFC: 102.3.1 Change of use or occupancy, notification. The responsible person shall forward a notification of the change in occupancy to the Eugene Springfield Office of the Fire Marshal in order to update fire department records within 30 days of the change. Exception: This requirement does not apply to Group R and U occupancies. 4. Section 105.5 of the OFC is amended to provide: 105.5 Required operational permits. In addition to any permits required by state law or administrative rule adopted by the Oregon Department of the State Fire Marshal, operational permits shall be obtained from the Eugene Springfield Office of the Fire Marshal prior to conducting any activities or operations listed in Sections 105.5 through 105.5.64. 5. Section 105.5B of the OFC is amended to provide: 105.5B Fireworks, public display of. An operational permit for the public display of fireworks is required under ORS 480.130. Applicants shall refer to subsections 105.5B.1 through 105.5B.2 of the Eugene Fire Code to determine the type of operational permit that is required. Operational permits issued under this section do not authorize any activity prohibited by section 4.934 of the Eugene Code (EC). An operational permit from the Eugene Springfield Office of the Fire Marshal does not remove or replace any requirement to obtain approval or permit from the Oregon Department of the State Fire Marshal. For general displays as defined in subsection 105.5B.2 that are conducted during a time other than the period of July 3 through July 5, consistent with EC 4.934, an applicant must obtain prior approval from the City Manager’s Office. The Fire Code Official will coordinate any approval required from the City Manager’s Administrative Order - Page 3 of 17 Office. A complete application, including a site plan and documentation required by Chapter 56 of this code and NFPA 1123 Code for Fireworks Displays (2022 edition), must be submitted not less than 60 days before any “general” display. 6. The following Sections 105.5B.1 and 105.5B.2 are added to the OFC. 105.5B.1 Fireworks, limited display. An operational permit is required for limited firework displays as defined in OAR 837-012-0720 that include displays held outdoors limited to 1.4G fireworks labeled UN0336. Fireworks authorized by the limited permit are subject to limitations by the local fire authority and the Oregon Department of the State Fire Marshal. 105.5B.2 Fireworks, general display. An operational permit is required for general fireworks displays as defined in OAR 837-012-0720 that include displays held outdoors, utilizing 1.3g fireworks and may include 1.4g fireworks and special effects fireworks and may only be conducted by a general display operator. 7.Section 105.5C (Fireworks Retail Sales) of the OFC is deleted. 8. Section 105.5.9 of the OFC is amended to provide: 105.5.9 Compressed gases. An operational permit is required for the storage, use or handling at normal temperature and pressure (NTP) of compressed gases in excess of the amounts listed in Table 105.5.9. Reference: section 105.5.23. Exception: Vehicles equipped for and using compressed gas as a fuel for propelling the vehicle. 9. Section 105.5.11 of the OFC is amended to provide: 105.5.11 Cryogenic fluids. An operational permit is required to produce, store, transport on site, use, handle or dispense cryogenic fluids in excess of the amounts listed in Table 105.5.11. Reference: section 105.5.23. Exception: Permits are not required for vehicles equipped for and using cryogenic fluids as a fuel for propelling the vehicle or for refrigerating the lading. 10.Section 105.5.19 of the OFC is amended to provide: 105.5.19 Flammable and combustible liquids. An operational permit is required: 1. To use or operate a pipeline for the transportation within facilities of flammable or combustible liquids. This requirement shall not apply to the off-site transportation in pipelines regulated by the Department of Transportation (DOTn), nor does it apply to piping systems. 2. To store, handle or use Class I liquids in excess of 5 gallons (19 L) in a building or in excess of 10 gallons (37.9 L) outside of a building, except that a permit is not required for the following: Administrative Order - Page 4 of 17 2.1. The storage or use of Class I liquids in the fuel tank of a motor vehicle, aircraft, motorboat, mobile power plant or mobile heating plant, unless such storage, in the opinion of the Fire Code Official, would cause an unsafe condition. 2.2. The storage or use of paints, oils, varnishes or similar flammable mixtures where such liquids are stored for maintenance, painting or similar purposes for a period of not more than 30 days. 3. To store, handle or use Class II or Class IIIA liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227L) outside a building, except for fuel oil used in connection with oil-burning equipment. 4. To store, handle or use Class IIIB liquids in tanks or portable tanks for fueling motor vehicles at motor fuel-dispensing facilities or where connected to fuel-burning equipment. Exception: Fuel oil and used motor oil used for space heating or water heating. 5. To remove Class I or II liquids from an underground storage tank used for fueling motor vehicles by any means other than the approved, stationary on-site pumps normally used for dispensing purposes. 6. To operate tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used. 7. To place temporarily out of service (for more than 90 days) an underground, protected above- ground or above-ground flammable or combustible liquid tank. 8. To change the type of contents stored in a flammable or combustible liquid tank to a material that poses a greater hazard than that for which the tank was designed and constructed. 9. To manufacture, process, blend or refine flammable or combustible liquids. 10. To engage in the dispensing of liquid fuels into the fuel tanks of motor vehicles at commercial, industrial, governmental or manufacturing establishments in accordance with Section 5706.5.4 or to engage in on-demand mobile fueling operations in accordance with Section 5707. 11.To utilize a site for the dispensing of liquid fuels from tank vehicles into the fuel tanks of motor vehicles, marine craft and other special equipment at commercial, industrial, governmental or manufacturing establishments in accordance with Section 5706.5.4 or, where required by the Fire Code Official, to utilize a site for on-demand mobile fueling operations in accordance with Section 5707. 12.Reference: section 105.5.23. 11. The following section 105.5.20 (Floor Finishing) of the OFC is deleted. 12.Section 105.5.23 of the OFC is amended to provide: 105.5.23 Hazardous materials permit. An operational permit is required to store, transport on site, dispense, use, or handle hazardous materials in excess of the quantities set forth in Tables 105.5.9, 105.5.11, 105.5.23, and Section 105.5.19. The permit issued under this section shall serve as the single annual hazardous materials operational reporting permit for a location and shall include all materials regulated under the referenced tables and sections when permit thresholds are exceeded and reported on the facility’s Hazardous Material Inventory Statement (HMIS). Facilities shall submit one HMIS annually identifying all qualifying hazardous Administrative Order - Page 5 of 17 materials at the site. The HMIS shall be submitted in the format prescribed by the Fire Code Official. The number of qualifying materials reported shall determine the applicable annual permit fee in accordance with Sections 105.5.23.1 through 105.5.23.6 and the adopted Community Risk Reduction & Resilience Division comprehensive fee schedule. 13. Sections 105.5.23.1, 105.5.23.2, 105.5.23.3, 105.5.23.4, 105.5.23.5, and 105.5.23.6 have been added to the OFC. 105.5.23.1 Hazardous materials, 1 to 4 materials reported. An operational permit is required to store, transport on site, dispense, use, or handle one (1) to four (4) hazardous materials in excess of the amounts listed in Tables 105.5.9, 105.5.11, 105.5.23, and Section 105.5.19. 105.5.23.2 Hazardous materials, 5 to 10 materials reported. An operational permit is required to store, transport on site, dispense, use, or handle five (5) to ten (10) hazardous materials in excess of the amounts listed in Tables 105.5.9, 105.5.11, 105.5.23, and Section 105.5.19. 105.5.23.3 Hazardous materials, 11 to 20 materials reported. An operational permit is required to store, transport on site, dispense, use, or handle eleven (11) to twenty (20) hazardous materials in excess of the amounts listed in Tables 105.5.9, 105.5.11, 105.5.23, and Section 105.5.19. 105.5.23.4 Hazardous materials, 21 to 30 materials reported. An operational permit is required to store, transport on site, dispense, use, or handle twenty-one (21) to thirty (30) hazardous materials in excess of the amounts listed in Tables 105.5.9, 105.5.11, 105.5.23, and Section 105.5.19. 105.5.23.5 Hazardous materials, 31 to 50 materials reported. An operational permit is required to store, transport on site, dispense, use, or handle thirty-one (31) to fifty (50) hazardous materials in excess of the amounts listed in Tables 105.5.9, 105.5.11, 105.5.23, and Section 105.5.19. 105.5.23.6 Hazardous materials, 50 or more materials reported. An operational permit is required to store, transport on site, dispense, use, or handle fifty (50) or more hazardous materials in excess of the amounts listed in Tables 105.5.9, 105.5.11, 105.5.23, and Section 105.5.19. 14. Sections 105.5.60, 105.5.61, 105.5.62, 105.5.63 and 105.5.64 have been added to the OFC: 105.5.60 Distressed property survey. An operational permit is required for the Office of the Fire Marshal to conduct a survey of vacant or abandoned premises, buildings, or structures (distressed property) to determine if the property poses a clear and inimical threat to human life, safety, or health. Administrative Order - Page 6 of 17 105.5.61 Fire art performance. An operational permit is required to conduct a fire art performance in a public or private location. 105.5.62 Places of temporary assembly. An operational permit is required to allow temporary assembly occupancy in a space not normally utilized as an assembly occupancy. This permit is required when the space to be utilized has not been previously classified as or approved for Assembly use by the Building Official. This permit is not intended to substitute for compliance with code requirements for an Assembly occupancy. The issuance of a places of temporary assembly operational permit is at the sole discretion of the Fire Code Official and may include additional safeguards. 105.5.63 Prescribed burning. An operational permit is required for any planned ignition of vegetation or combustible materials conducted for fuel reduction, wildfire risk mitigation, or ecological management. 105.5.64 Unique conditions. An operational permit is required for an existing or proposed activity, building or structure, or for the safety of the occupants thereof which is not specifically provided for by this code as determined by the Fire Code Official as referenced in Section 102.9 of this code. 15. Section 108.2 of the OFC is amended to provide: 108.2 Schedule of permit fees. A fee for each permit shall be paid as required, in accordance with the applicable fee schedule established by the City Manager pursuant to Section 2.020 of the Eugene Code, 1971. 16. Section 110.1.1 of the OFC is amended to provide: 110.1.1 Access to safeguards. Any device, equipment, system, condition, arrangement, level of protection, or any other feature required for compliance with the provisions of this code, or otherwise installed, shall be continuously maintained accessible and unobstructed. 17. Section 112.1 of the OFC is amended to provide: 112.1 Appeals. Any person aggrieved by an action taken pursuant to this code may appeal the action within the time and in the manner provided in section 2.021 of the Eugene Code, 1971. 18. Sections 112.2 (Limitations on authority), 112.3 (Qualifications), and 112.4 (Administration) of the OFC are deleted. 19. Section 113.4.1 of the OFC is amended to provide: 113.4.1 Local penalties. Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in Administrative Order - Page 7 of 17 violation of the approved construction documents or directive of the Fire Code Official, or of a permit or certificate used under provisions of this code, shall be subject to an administrative civil penalty imposed pursuant to EC 2.018, including the compliance opportunity and procedural requirements therein, and subject to appeal as provided by EC 2.021. Each day that a violation continues after due notice has been served shall be deemed a separate violation. 20. Section 202 of the OFC is amended by adding the following definitions in alphabetical order: ABANDONED PROPERTY: Premises, buildings, or structures where there is no visible or definitive owner/landlord, or one that cannot clearly be identified or contacted. CARNIVAL. A mobile enterprise principally devoted to offering amusement or entertainment to the public in, upon or by means of portable amusement rides or devices or temporary structures in any number or combination, whether or not associated with other structures or forms of public attraction. DISTRESSED PROPERTY. Any property, premises, building, or structure that is abandoned, vacant, or transitional and that, due to structural instability, deterioration, neglect, unsecured access, accumulation of combustible materials, impaired or disconnected utilities including water supply, incomplete construction, or unsafe occupancy, constitutes or contributes to an unsafe building, premises, or structure as defined by the Oregon Fire Code. Distressed property includes conditions involving recreational vehicles, vehicles, tents, or temporary shelters used for habitation where such conditions increase fire risk, obstruct access or egress, impair available fire protection or firefighter operations, or otherwise create fire and life safety hazards, and may require corrective action or abatement. EUGENE CODE (EC). The Eugene Code, 1971. FIRE ART PERFORMANCE. Any act of fire juggling, fire eating, flame effects, etc. that utilizes fire for entertainment purposes, conducted in an outdoor public or private place (other than inside a private residence) outside of a protective housing or in ways in which travels through the air by one person or between multiple persons. KEYHOLDER: A person or agency who has been designated as the responsible party and after hours point of contact to provide access to all areas of a property, building, or structure. Keyholders must possess the keys, key cards, door codes, alarm codes, and the requisite knowledge necessary to provide first responders the access and ability to mitigate any emergency. PRE-INCIDENT PLAN. A document developed by gathering general and detailed data to be used by responding personnel in effectively managing emergencies for the protection of occupants, participants, responding personnel, property, and the environment. Administrative Order - Page 8 of 17 RED FLAG CRITERIA: Red Flag Criteria occurs whenever a geographical area has been in a dry spell for one to two weeks, or for a shorter period, if before spring green-up or after fall color, and the National Fire Danger Rating System (NFDRS) is high to extreme and the following forecast weather parameters are forecasted to be met: 1. a sustained wind average 15 mph or greater. 2. relative humidity less than or equal to 25 percent and, 3. a temperature of greater than 75 degrees F. RED FLAG WARNING. A term used by fire-weather forecasters to call attention to limited weather conditions of particular importance that may result in extreme burning conditions. Red flag warnings are issued for ongoing events, or when the fire weather forecaster has a high degree of confidence that Red Flag criteria will occur within 24 hours of issuance. TRANSITIONAL PROPERTY: Premises, buildings, or structures that are uninhabited while in the process of a change in ownership; for example, the sale and transfer of ownership of a single-family residential dwelling. VACANT PROPERTY: Premises, buildings or structures that may be empty or unoccupied, but there exists an owner with an expressed interest in the property. 21. The definitions of the terms “Fire Code Official,” “Open Burning,” and “Recreational Fire” in Section 202 of the OFC are amended as follows: FIRE CODE OFFICIAL. The Eugene Springfield Fire Marshal, or duly authorized representative, is designated as the approved authority for exercising functions relating to fire prevention, fire safety measures and the administration and enforcement of this code. OPEN BURNING. The burning of materials wherein products of combustion are emitted directly into the ambient air without passing through a stack or chimney from an enclosed chamber or as regulated by Lane Regional Air Protection Agency and EC 6.200. Open burning does not include road flares, smudge pots and similar devices associated with safety or occupational uses, typically considered open flames or recreational fires. For the purpose of this definition, a chamber shall be regarded as enclosed when, during the time combustion occurs, only apertures, ducts, stacks, flues, or chimneys necessary to provide combustion air and permit the escape of exhaust gas are open. RECREATIONAL FIRE. An outdoor fire with a total fuel area not exceeding 3 feet in diameter and 2 feet in height, used for pleasure, warmth, cooking, religious, or ceremonial purposes, and fueled only by charcoal, natural gas, propane, manufactured fire logs, or clean, dry natural firewood. Recreational fires may occur in approved fire pits, chimineas, patio or outdoor fireplaces, or similar appliances, or as open fires in designated areas on public or private property and shall not be used for the disposal of rubbish or waste materials, including woody yard debris, leaves, or grass clippings. Administrative Order - Page 9 of 17 22.Section 302.1 is amended to add the following to the list of terms in that section: FIRE ART PERFORMANCE RED FLAG CRITERIA RED FLAG WARNING 23. The following section 305.4.1 is added to the OFC: 305.4.1 Extreme burning conditions. Use of open flames or other sources of ignition that could ignite vegetation or combustible material during a Red Flag Warning is prohibited and is considered an emergency requiring immediate abatement. 24. Section 308.2 of the OFC is amended to provide: 308.2 Permits required. Permits shall be obtained from the Fire Code Official in accordance with Section 105.5 prior to engaging in the following activities involving open flame, fire and burning: 1.Use of a torch or flame-producing device to remove paint from a structure. 2. Use of open flame, fire or burning in connection with Group A or E occupancies. 3.Use or operation of torches and other devices, machines or processes liable to start or cause fire in or on wildfire risk areas. 4.Fire art performances. 25.Sections 311.5 and 311.5.1 of the OFC are amended to provide: 311.5 Placards. Any vacant or abandoned premises, buildings, or structures determined to be unsafe pursuant to section 115 of this code relating to structural or interior hazards shall be placarded as required by Sections 311.5.1 through 311.5.5 of this code and any applicable policies, ordinances, or administrative orders of the City of Eugene. 311.5.1 Placard location. Placards shall be installed on the front of the structure in a location clearly visible from the street or fire apparatus access road and mounted at an elevation not less than 8 feet and not more than 12 feet above finished grade to limit tampering and ensure visibility to responding personnel. Additional placards shall be installed at the side of each entrance to the structure and on penthouses at the same elevation, unless the Fire Code Official approves an alternate location that provides equivalent visibility and protection from tampering. 26. Section 311.5.2 of the OFC is amended to provide: 311.5.2 Placard size and color. Except as provided in section 311.5.2.1, the size and color of placards used to identify the status of premises, buildings, or structures in the City of Eugene shall be as follows: Administrative Order - Page 10 of 17 1. UNSAFE or “U” placards shall be 24” x 24” square, red background with 2” wide white reflective border. White reflective letter “U” 18” x 18”, with a 2” minimum stroke width. The letter shall be arial font or similar. 2. CAUTION or “C” placards shall be 24” x 24” square, orange background with 2” wide white reflective border. White reflective letter “C” 18” x 18”, with a 2” minimum stroke width. The letter shall be arial font or similar. 3. SAFE or “S” placards shall be 24” x 24” square, green background with 2” wide white reflective border. White reflective letter “S” 18” x 18”, with 2” minimum stroke width. The letter shall be arial font or similar. 27. The following section 311.5.2.1 is added to the OFC. 311.5.2.1 Placard size and color. The size and color of placards used to identify the status of residential premises, buildings, or structures in the City of Eugene shall be as follows: 1. UNSAFE or “U” placards shall be 16” x 16” square (15.875” X 15.875” nominal), with red background and a 1” wide white reflective border. The white reflective letter “U” will measure 11.5” X 11.5” with a 2.25” minimum stroke width. The letter shall be arial font or similar. 2. CAUTION or “C” placards shall be 16” x 16” square (15.875” X 15.875” nominal), with orange background and a 1” wide white reflective border. The white reflective letter “C” will measure 11.5” X 11.5” with a 2.25” minimum stroke width. The letter shall be arial font or similar. 3. SAFE or “S” placards shall be 16” x 16” square (15.875” X 15.875” nominal), with green background and a 1” wide white reflective border. The white reflective letter “S” will measure 11.5” X 11.5” with a 2.25” minimum stroke width. The letter shall be arial font or similar. 28. Section 311.5.4 of the OFC is amended to provide: 311.5.4 Placard Symbols. The design of placards shall use the following symbols: 1. This symbol shall mean that the structure had normal structural conditions at the time of marking. 2. This symbol shall mean that structural or interior hazards exist, and interior firefighting or rescue operations should be conducted with extreme caution. Administrative Order - Page 11 of 17 3. This symbol shall mean that structural or interior hazards exist to a degree that consideration should be given to limit firefighting to exterior operations only, with entry only occurring for known life hazards. 29. The following section 401.9 is added to the OFC: 401.9 Evacuation Required. In the event of an activation of a fire alarm, emergency alarm, or at the direction the Fire Code Official, occupants of the building or portion of the building in which the alarm is activated shall make a safe and orderly evacuation out of the building, or as provided in the building’s fire safety, evacuation, or emergency operations plan. Exceptions: 1. Where an occupant’s disability makes the occupant unable to evacuate without assistance and no assistance is immediately available; or 2. Where the presence of smoke, fire, structural collapse or other hazard or obstruction in the occupant’s means of egress makes evacuation unsafe. 30. Section 403.11.3.2 of the OFC is amended to provide: 403.11.3.2 Training. Training for crowd managers shall be approved and verified by the Fire Code Official. 31. Section 406.3 of the OFC is amended to provide: 406.3 Employee training program. Employees shall be trained in fire prevention, evacuation, defend-in-place, emergency lockdown training, and fire safety in accordance with Sections 406.3.1 through 406.3.5. 32. The following section 406.3.5 is added to the OFC: 406.3.5 Defend-in-place training. Where a facility has a defend-in-place plan, the facility’s employees shall be trained on the alert and recall signals, communication system, location of emergency supplies, the use of the incident notification and alarm system, and their assigned duties and procedures in the event of an alarm or emergency. 33. The following Section 408 is added to the OFC: 408.1 General. Where required by the Fire Code Official, a pre-incident plan shall be submitted in accordance with Section 408.2 through Section 408.2.8 Administrative Order - Page 12 of 17 408.2 Fire Department Pre-Incident Plans. Where required by the Fire Code Official, an approved electronic pre-incident plan containing current site drawings and floor plans for an occupancy, structure, development, or facility shall be provided to the fire department for planning purposes. The electronic submittal shall conform to the fire department specifications and shall be received and approved by the Fire Code Official prior to the fire department’s recommendation for occupancy approval by the Building Official. The electronic pre-incident plan may include information required for a Building Information Card but shall not replace any requirement for a physical Building Information Card where otherwise required by this code. 408.2.1 Building Information Card. A Building Information Card (BIC) shall be provided for buildings or facilities where the size, height, occupant load, configuration, use, licensing status, or presence of special hazards presents a level of complexity or risk that would reasonably benefit emergency responders, as determined by the Fire Code Official. This includes, but is not limited to, high-rise and underground buildings, buildings with large occupant loads, atriums, multiple buildings on a common podium, covered malls, and residential occupancies subject to state licensure. Where a fire command center is provided, the Building Information Card shall be located within the fire command center. Where no fire command center exists, the Building Information Card shall be located in an approved location near the fire alarm control panel. The Building Information Card shall include, at a minimum, the information specified in Sections 408.2.2 through 408.2.8. 408.2.2 General building information. General building information required for a Building Information Card and an electronic pre-incident plan shall include the property name and address; number of floors above and below grade; use and occupancy classification, including identification of mixed occupancies by floor; and the estimated building population during daytime, nighttime, and weekend conditions. 408.2.3 Building emergency contact information. Building emergency contact information required for a Building Information Card and an electronic pre-incident plan shall include a list of emergency contacts with current work phone numbers, mobile phone numbers, and email addresses, including, at a minimum, the building manager and building engineer. 408.2.4 Building construction information. Building construction information required for a Building Information Card and an electronic pre-incident plan shall include the building construction type and the primary structural elements, including floors, walls, columns, and roof assemblies. 408.2.5 Exit stairway and elevator information. Exit stairway and elevator information required for a Building Information Card and an electronic pre-incident plan shall include the number, designation, and floors served by exit access stairways, exit stairways, and elevator banks; discharge locations; stairway features affecting firefighter operations, including pressurization, emergency lighting, reentry, and roof access; and the locations of elevator machine rooms, control rooms or spaces, sky lobbies, and freight elevator banks. Administrative Order - Page 13 of 17 408.2.6 Building services and system information. Building services and system information required for a Building Information Card and an electronic pre-incident plan shall include the locations of mechanical rooms, building management system controls, emergency generators, fuel oil tanks and their capacities, and natural gas service. 408.2.7 Fire protection system information. Fire protection system information required for a Building Information Card and an electronic pre-incident plan shall include the locations of standpipes, fire pump rooms, fire department connections, and system control points; the floors protected by automatic sprinkler systems; and the locations and types of fire suppression systems installed, including wet, dry, and pre-action sprinkler systems. 408.2.8 Hazardous material information. Hazardous material information required for a Building Information Card and an electronic pre-incident plan shall include the location and general quantity of hazardous materials, as defined by this code, present within the building or facility. 34. Section 503.2.7 of the OFC is amended to provide: 503.2.7 Grade. The grade of the fire apparatus access road shall be in accordance with the Eugene Code. Access roads, including public and private roads and driveways shall comply with the following: 1. The grade of access for non-sprinklered properties shall not exceed 10%. 2. The grade of access for sprinklered properties shall not exceed 12%. 3. All grades of access exceeding 12% require approval by the Fire Code Official. 35. Section 503.6 of the OFC is amended to provide: 503.6 Security gates, bollards, and obstructions. The installation of security gates, bollards, or other obstructions across a fire apparatus access road shall be subject to review and approval by the Fire Code Official. Directional-limiting devices, including tire spikes, are prohibited. Where security gates, bollards or other obstructions are installed, such devices shall be provided with an approved and continuously maintained means of emergency operation readily accessible to responding fire personnel. Electric gate operators shall be listed in accordance with UL 325. Gates intended for automatic operation shall be designed, constructed, and installed in accordance with ASTM F2200 and shall be equipped with Click2Enter technology or other approved equipment that allows operation by fire personnel from fire apparatus. Exceptions: 1. Gates shall be not less than the required width of the fire apparatus access road. 2. On commercial properties, gates, bollards, or other obstructions shall be set back a minimum of 30 feet from the roadway edge of pavement. 3. Where fencing is provided on both sides of a gate on commercial properties, a man door shall be provided at an approved location and equipped with an approved key box. 4. Automated gates equipped with Click2Enter technology or other approved equipment allowing operation by fire personnel from fire apparatus shall not be required to comply with Administrative Order - Page 14 of 17 the 30-foot setback, provided the roadway is not an arterial, residential collector street, or a street with lane markings. 36. Section 606.5 of the OFC is added to provide: 606.5 Commercial cooking systems. Automatic fire-extinguishing systems protecting commercial cooking equipment and exhaust systems shall be of a type recognized for the hazard and arrangement protected and shall be listed, labeled, and installed in accordance with this code, NFPA 96, the system listing, and the manufacturer’s installation instructions. Pre- engineered dry-chemical and wet-chemical extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. Other types of automatic fire- extinguishing systems shall be listed and labeled for use in commercial cooking operations. Signage shall be provided on the exhaust hood or system cabinet identifying the cooking appliances protected by the extinguishing system, listed from left to right. Signage shall be durable, and the size, color, and lettering shall be approved by the Fire Code Official. Automatic fire-extinguishing systems shall be installed in accordance with the applicable standard as follows: 1. Carbon dioxide systems: NFPA 12 2.Automatic sprinkler systems: NFPA 13 3.Water mist systems: NFPA 750 4.Foam-water sprinkler or foam-water spray systems: NFPA 16 5.Dry-chemical systems: NFPA 17 6.Wet -chemical systems: NFPA 17A Exception: Factory-built commercial cooking recirculating systems tested in accordance with UL 710B and listed, labeled, and installed in accordance with Section 304.1 of the International Mechanical Code. 37. Section 901.4.2 of the OFC is amended to provide: 901.4.2 Nonrequired fire protection and life safety systems. Fire protection and life safety systems, or portions thereof, not required by this code or the International Building Code may be provided for partial or complete protection, provided such systems comply with the applicable requirements of this code and the International Building Code. Systems or portions of systems not required by code shall be identified with durable, permanent signage stating “NON- REQUIRED SYSTEM,” with contrasting color and background and lettering not less than 1 inch (25.4 mm) in height. The location of such signage shall be approved by the Fire Code Official. 38. Section 901.6.3 of the OFC is amended to provide: 901.6.3 Records. Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained. Fire protection and life safety system service providers shall submit all reports through The Compliance Engine (TCE) or as otherwise required by the Fire Code Official. Administrative Order - Page 15 of 17 39. The following section 901.6.4 is added to the OFC: 901.6.4 Excessive false automatic fire alarm activation. Excessive fire alarm (nuisance fire alarm) activations. Preventable activations of fire alarm and life safety systems that results in the fire department’s response and arrival at the occupancy of an alarm in excess of three (3) preventable alarms in a twelve (12) month period may be cited and restitution sought under the provisions this code, applicable administrative orders, or ordinances of the City of Eugene. 40. Section 5001.5.2 of the OFC is amended to provide: 5001.5.2 Hazardous materials inventory statement (HMIS). Where required by the Fire Code Official, an application for a permit shall include an HMIS, such as Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report, or other approved statement. The HMIS shall include the following information: 1. Product name. 2. Component. 3. CAS - Chemical Abstract Service Number. 4. Location where stored or used. 5. Container size. 6. Hazard classification. 7. Amount in storage. 8. Amount in use - closed systems. 9. Amount in use - open systems. 10. NFPA 704 classification. 41. The following standards are added in numerical order to the list of National Fire Protection Association (NFPA) standards included in Chapter 80 of the OFC: 3 - 24: Standard for Commissioning of Fire Protection and Life Safety Systems 13E - 26: Recommended Practice for Fire Department Operations in Properties Protected by Sprinkler and Standpipe Systems 36 - 25: Standard for Solvent Extraction Plants 51B - 24: Standard for Fire Prevention During Welding, Cutting, and Other Hot Work 54 - 24: National Fuel Gas Code 88A - 23: Standard for Parking Structures 99B - 24: Standard for Hypobaric Facilities 102 - 26: Standard for Grandstands, Folding and Telescopic Seating, Tents, and Membrane Structures 291 - 25: Recommended Practice for Water Flow Testing and Marking of Hydrants 420 - 25Standard on Fire Protection of Cannabis Growing and Processing Facilities 440 - 24: Guide for Aircraft Rescue and Firefighting Operations and Airport/Community Emergency Planning 455 - 26: Standard for Emergency Medical Services (EMS) Administrative Order - Page 16 of 17 460 - 26: Standard for Aircraft Rescue and Firefighting Services at Airports 502 - 26: Standard for Road Tunnels, Bridges, and Other Limited Access Highways 915 - 24: Standard for Remote Inspections and Tests 921 - 24: Guide for Fire and Explosion Investigations 1006 - 21: Standard for Technical Rescue Personnel Professional Qualifications 1010 - 24: Standard on Professional Qualifications for Firefighters 1020 - 25: Standard for Fire and Emergency Services Instructor, Fire Officer, and Emergency Medical Services Officer Professional Qualifications 1030 - 24: Standard for Professional Qualifications for Fire Prevention Program Positions 1033 - 22: Standard for Professional Qualifications for Fire Investigator 1140 - 22: Standard for Wildland Fire Protection 1145 - 22: Guide for the Use of Class A Foams in Fire Fighting 1300 - 26: Standard on Community Risk Assessment and Community Risk Reduction Plan Development 1321 - 25: Standard for Fire Investigation Units 1400 - 26: Standard on Fire Service Training 1550 - 24: Standard for Emergency Responder Health and Safety 1580 - 25: Standard for Emergency Responder Occupational Health and Wellness 1585 - 25: Standard for Exposure and Contamination Control 1660 - 24: Standard for Emergency, Continuity, and Crisis Management: Preparedness, Response, and Recovery 1700 - 26: Guide for Structural Fire Fighting 1750 - 26: Standard for the Organization and Deployment of Fire Suppression Operations, Emergency Medical Services, Special Operations, and Fire Prevention Activities 1850 - 26: Standard on Selection, Care, and Maintenance of Protective Ensembles for Structural and Proximity Firefighting and Open-Circuit Self-Contained Breathing Apparatus (SCBA) 1857 - 26: Standard on Selection, Care, and Maintenance of Protective Ensembles for Technical Rescue Incidents and Wildland Firefighting 1900 - 24: Standard for Aircraft Rescue and Firefighting Vehicles, Automotive Fire Apparatus, Wildland Fire Apparatus, and Automotive Ambulances 1910 - 24: Standard for the Inspection, Maintenance, Refurbishment, Testing, and Retirement of In-Service Emergency Vehicles and Marine Firefighting Vessels 1930 - 25: Standard on Fire and Emergency Service Use of Thermal Imagers, Two-Way Portable RF Voice Communication Devices, Ground Ladders, Rescue Tools, Fire Hose, and Fire Hose Appliances 1950 - 25: Standard on Personal Protective Equipment for Technical Rescue Incidents, Emergency Medical Operations, and Wildland and Urban Interface Firefighting 1960 - 24: Standard for Fire Hose Connections, Spray Nozzles, Manufacturer's Design of Fire Department Ground Ladders, Fire Hose, and Powered Rescue Tools Mc ~ 1970 -25: Standard on Protective E nsembles for Structural and Proximity Firefighting, Work Apparel, Open-Circuit Self-Contained Breathing Apparatus (SCBA) for Emergency Services, and Personal Alert Safety Systems (PASS) 1990 -22: Standard for Protective Ensembles for Hazardous Materials and CBRN Operations 2500 -22: Standard for Operations and Training for Technical Search and Rescue Incidents and Life Safety Rope and Equipment for Emergency Services 3000 -24: Standard for an Active Shooter/Hostile Eve nt Response (ASHER) Program APPENDIXD FIRE APPARATUS ACCESS ROADS Section DlOl General 42. Section Dl0l.1 of Appendix D to the OFC is amended to provide: DlOl.1 Scope. Fire apparatus access roads shall be in accordance with this appendix and all other applicable requirements of the Eugene Fire Code. The Fire Code Official may be guided by adopted City of Eugene street standards for grade and hillside development requirements. City streets shall conform to design standards as set forth in the adopted City of Eugene street standards. 43. Section D102.1 of Appendix D to the OFC is amended to provide: D102.1 Access and loading. Facilities , buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighing up to 86,000 pounds . 44. Section D103.2 of Appendix D to the OFC is amended to provide: Grade. The grade of the fire apparatus access road shall be in accordance with the Eugene City Code. Access roads, including public and private roads and driveways shall comply with the following: 1. The grade of access for non-sprinklered properties shall not exceed 10%. 2. The grade of access for sprinklered properties shall not exceed 12%. 3. All grades of access exceeding 12% require approval by the Fire Code Official. Dated this__!_§_ day of June, 2026. Administrative Order -Page 17 of 1 7 Jennifer D. Haruyama City Manager ~ 18:19 :55 PDT ) Exhibit A to Administrative Order No. 52-26-02 NOTICE OF OPPORTUNITY TO COMMENT ON PROPOSED AMENDMENT OF EUGENE FIRE CODE ADMINISTRATIVE RULE R-8.010FC. Pursuant to Sections 2.019 and 8.010 of the Eugene Code, 1971, the City Manager is proposing to amend Eugene Fire Code Administrative Rule R-8.010FC so that the City of Eugene’s Fire Code will be consistent with the 2025 Oregon Fire Code, and to maintain a reasonable degree of fire and life safety for the community at large. The principal document relied upon by the City in considering the need for and in preparing this Rule is the 2025 Oregon Fire Code which can be viewed online at https://codes.iccsafe.org/content/ORFC2022P1, or by calling the Fire Marshal’s Office at 541- 682-5411 to make an appointment to review the document. The proposed Rules may be reviewed on the City of Eugene’s website at https://www.eugene- or.gov/520/Administrative-Order or on the Fire Marshal’s Office’s website at https://eugene- or.gov/125/Fire-Marshal; or by emailing FMOAdmin@ci.eugene.or.us to request a copy of the document; or by calling the Fire Marshal’s Office at 541-682-5411 to make an appointment to review the document. Comments on the proposed Rules should be submitted in writing to the Fire Marshal, 1320 Willamette Street, Eugene, Oregon, 97401, or via e-mail to FMOAdmin@ci.eugene.or.us. To be considered, written and e-mail comments must be received within 15 days of the first date of publication as indicated below. If the City Manager chooses to take action after considering the comments received, the proposed or modified rule will be adopted by administrative order. Jennifer D. Haruyama, City Manager Dates of Publication: June 17, 18, 19, 21, and 22, 2026. Notice - Page 1 of 1