Laserfiche WebLink
4~3 <br />- - - <br />- - k~- _._._ -_ __._ - _ _._ ___ __..-___-.-_. _____ ___ _ __ __-___ _..-_ <br />(c) Openings, if any, between vault and main building shall be protected on <br />each side of the wall by an approved fire door. Wall openings in outside vaults exposing <br />other property (not sufficiently detached to be considered cut off) shall be protected <br />by approved fire doors or equivalent. <br />(d) Vaults located Tprithin buildings and exceeding 1,000 cubic feet storage <br />capacity shall be protected by approved automatic sprinklers, if possible. Ulhere such <br />protection is not available steam jets or inert gas systems ap~oroved for fire extinguish- <br />ing purposes shall be installed. <br />1~G5. 1`Tot to exceed 2,500 cubic feet of looses fibre may be stored in detached "loose <br />house" suitably located, ~rrith openings properly protected against entrance of sparks. <br />The "1-Dose house" shal_1 be used for no other purpose. <br />1~0 Blocks or piles of baled fibre shall be separated from adjacent storage by <br />aisles not less than 5 feet wide; or by flash fire barriers consisting of continuous <br />sheets of non-combustible material extending-from floor to a height of at least one foot <br />beyond the sides of the piles. , <br />1+08. Sisal and other fibres in bales bound ~,uith combustible tie ropes, also jute and <br />other fibres liable to sr,uell when wet, shall be stored to allow for ex~oansion to the extent <br />of 20 per cent of their bulk in any direction without endangering building walls, ceilings <br />or columns. Not less than e feet clearance shall be maintained bet~r~een sprinkler pipes <br />and tops of piles. Not less than j feet clearance shall be left bet~rreen galls and sides <br />of piles, except that if storage compartment is not more than 30 feet in width, one foot <br />clearance at side ~;ralls will be sufficient, provided a ten ter aisle not less than 5 feet <br />t,~ide is maintained. <br />1~-QG. Unlimited quantities of hay, straw, and other agricultural products may be <br />stored in or near farm buildings located outside closely-built areas. <br />PART 15. <br />REFRIGERATIGN. <br />1 O1. (a} No installation of a refrigerating unit or system containing in excess of <br />20 pounds of refrigerant shall be made until a permit has been obtained from the Bureau <br />of Fire Prevention, except that no permit shall be re:±uired for non-condensing refriger- <br />ating systems using-air as a refrigerant. <br />(b) Systems requiring a permit and containing any refrigerant ~rrhich is harmful <br />to health and. the vapors of ~•rhich are not readily apparent through odor or irritating <br />effect shall have added to such refrigerant a suitable leak detecting agent ~,rhich trill <br />give ~r~arriing before dangerous concentrations are reached. This restriction shall not <br />apply to systems employing carbon dioxide. <br />(c) For the purioose of this ordinance a '~Toxic~' refrigerant is one falling <br />in Under4rriters~ Laboratories, Inc. toxicity classification Groups 1 to ~+ inclusive. The <br />following refrigerants are toxic as thus defined, or are flammable or both toxic and <br />flammable. <br />Ammonia Ethane P~lethyl Bromide <br />Butane Ethyl Bromide Methyl Chloride <br />Dichlorethylene Ethyl.Chloride tdethyl Formate <br />Prooane Sulphur Dioxide <br />1 02. Except in plants used exclusively for ice making, refrigeration or cold storage <br />no system"containing over 100 pounds of toxic ~or flam-~able refrigerant shell be" instal- <br />led unless it conforms to the folloTrring provisions: <br />(a) Refrigeration shall be by the indirect method, except that direct refrig- <br />eration will be-permitted in rooms, vaults or other spaces used for storage only, or in <br />connection ~hrith a manufacturing process located on the ground floor only fl.nd with adequate <br />exit facilities. No brine circulating system employing a brine having a flash point <br />'below 1000 ~'. shall be permitted in any ].oca.tian in t;rhich an indirect system only is per- <br />missible. <br />(b) Each compressor shall be in -a special machinery room ~,aith suitable exit <br />to the outside. Adequate means for ventilation sha.11 be provided by a door or tvind.ow <br />opening to the outside or a mechanical system•of-ventilation-shall be provided. <br />(c) Remote control shall be provided. such .that all machinery can be shut down <br />~,vithout entering the machinery room. •- ---•---- •---~• • <br />(d) Suitable mask shall be provided, which shall be kept in operative condit- <br />ion in an easily accessible case or cabinet immediately outside the machinery room. <br />(e) All doorways betvreen the machinery"room and other -parts of the building <br />shall be normally closed and shall be tight-fitting. No other openings between the <br />machinery room and other parts of the building shall be permitted. <br />