Laserfiche WebLink
fib} Exterior Stora e. <br />~, General. Exterior storage of unstable reactive} mat- <br />erials shall be in accordance with the provisions of this sub- <br />section and the general provisions specified in Section 80.301. <br />z. Distance from Stora a to Ex osures. Exterior storage <br />of unstable reactive} materials shall not be permitted within <br />z0 feet of any building, property line, street, alley, public <br />way or exit to a public way. An unpierced two-hour fire- <br />resistive wall extending not less than 30" above and to the <br />sides of the storage may be provided in lieu of such distance. <br />EXCEPTION: unstable reactive} materials which may <br />deflagrate shall not be permitted within 75 feet of <br />any building, property line, street, alley, public <br />way or exit to a public way. <br />3. Containment. Secondary containment shall be pro- <br />vided in accordance with the provisions of Section 80.3011}4. <br />4. Stora a Conditions. <br />A. C1 ass 3 or 4 materials shall be limited to piles <br />not greater than 100 cubic feet. <br />B. Class 1 or z materi al s shal 1 be 1 imi ted to pi 1 es <br />not greater than 1,000 cubic feet. <br />C. Aisle widths between piles shall be not less than <br />one-half the height of the pile or 10 feet, whichever is <br />greater. <br />Section 80.310 -Hazardous Materials, Water-Reactive Materials. <br />~a} Indoor,,S,tora~e. <br />1. Generai~. Indoor storage of water-reactive materials <br />shall be in accordance with the provisions of this subsection <br />and the general provisions specified in Section 80.301. <br />2. Exempt Amounts. When the amount of water-reactive <br />materials stored~~~~~~~ n one control area exceeds that specified i n <br />Table 80.310-A, such storage shall be within a room or build- <br />ing conforming to the Structural Specialty Code requirements <br />fora Group H, Division 3 Occupancy. <br />Storage exceeding the exempt amounts specified in Table <br />80.310-A shall comply with items numbered z. through 10. <br />Storage not exceeding the exempt amounts specified in Table <br />80.310-A shall comply with item numbered 10.B. <br />Table 80.314-A <br />Condition <br />Unprotected by <br />or cabinet <br />Within cabinet <br />unsprinklered <br />I n spr i n k1 ered <br />not in cabine <br />In sprinklered <br />sprinklers <br />in <br />building <br />building, <br />t <br />building, <br />Exempt Amount (Pounds) <br />CL 1 CL 2 CL 3 CL 4 <br />within cabinet <br />NL: Not limited. <br />Far water-reactive <br />lz5 50 5 <br />250 10a 10 <br />NL 100 10 <br />NL zoo z0 <br />materials, a conversi on of 10 pounds per <br />Ordinance - 5z <br />