Laserfiche WebLink
of corrosive liquids shall not be permitted within 20 feet of <br />any building, property line, street, alley, public way or <br />exit to a public way. An unpierced two-hour fire-resistive <br />wall extending not less than 30" above and to the sides of the <br />storage area may be provided in lieu of such distance, <br />3. Containment. Secondary containment shall be provided <br />for the storage of corrosive liquids in accordance with the <br />requirements of Section 80.3011}4. <br />Section 50.315 - Hazardous Materials, Other Health Hazard Solids, <br />Li uids and Gases. <br />~a} Indoor Storage. <br />1. General. Indoor storage of other health hazard <br />solids, liquids, and gases shall be in accordance with the <br />provisions of 80.315~a} and ~c} and the general provisions <br />specified in Section 80.301. <br />z, Exem~t.Amounts. When the amount of other health <br />hazard solids, liquids, and gases exceeds that specified in <br />Table 80.315-A, such storage shall be within a room or build- <br />ing conforming to the Structural Specialty Code requirements <br />for a Group H, Division 7 Occupancy. <br />Condition <br />Unprotected by sprinklers <br />or cabinet <br />Within cabinet in <br />unspri nkl erect bui 1 di ng <br />In spri nkl erect bui 1 di ng, <br />not in cabinet <br />In spri nkl erect bui 1 di ng, <br />within cabinet <br />Table 80.315-A <br /> Exempt Rmount <br />Solids Li uids Gases <br />Pounds} Gallons} ~Cu Ft} <br />5,000 500 650 <br />10,000 1,000 1,300 <br />10,000 1,000 1,300 <br />zo, aoo z, oao z, 500 <br />3. Li uid-Ti ht Floor. In addition to the provisions of <br />Section 80.301~z}, floors of storage areas far other health <br />hazard liquids shall be of liquid-tight construction, <br />4. Ex losion Ventin or Su cession. Explosion venting <br />or suppression systems sha]i not be required for the indoor <br />storage of other health hazard sal ids, liquids, and gases. <br />5, Containment. Secondary containment shall be provided <br />in accordance with the provisions of Section 80.3011}4. <br />fib} Exterior Stora e. <br />1. General. Exterior storage of other health hazard <br />solids and liquids shall be in accordance with the provisions <br />of this subsection and the general provisions specified in <br />in Section 80.301. <br />z. Distance from Stora a to Ex osures. Exterior storage <br />of other health hazard solids, 1 i quids, and gases shal 1 not be <br />permitted within z0 feet of any building, property line, <br />street, alley, public way or exit to a public way. An un- <br />pierced two-hour fire-resistive wall extending not less than <br />Ordinance - 59 <br />