rd ;~~nan~e,.~ - <br />• ~~ <br />located above the openings. <br />~4} any other points necessary to ensure the <br />protection of the exit way. <br />b . A water supply shall be provided sufficient to <br />operate at 1 east five sprinkler heads simultaneously for <br />a period of 2D minutes at a residual pressure of not less <br />than 15 pounds a square inch at the highest head in the <br />system. Such supply may originate from: <br />~1} domestic water supply; <br />~Z} separate connections to public mains; <br />~3} on-site reservoirs or tanks, or <br />~4} wet standpipe lines. <br />c. Building fire-alarm systems shall be connected <br />to a sprinkler system water-flow device. <br />d. Systems shall be equipped with afire department <br />connection and a swing check valve an the supply side. <br />ExCEPTIaN: The fire department connection may be <br />. omitted when the water supply to the building is capable <br />of simultaneously operating the number of sprinkler heads <br />installed in the two largest separate areas which are <br />directly interconnected by a normally closed door, or <br />when waived by the fire chief. <br />2. Full fire ratection. Then required by other provi- <br />sions of this code, complete automatic fire extinguishing <br />systems and stand pipes shall be installed as specified in <br />Chapter 38. <br />fib} Grou SR, Division 2 occu ancy. ~- complete automatic <br />fire extinguishing system and stand pipes shall be installed as <br />specified in chapter 38 only when required by other provisions of <br />this code. <br />~4} Section 1313, Fire Alarms, fis hereby amended by adding an <br />additional paragraph at the end of the second paragraph to read; <br />The building owner or his designee shall inspect and service <br />each detector every six months. A record shall be maintained of <br />each detector ]fisting the date installed, dates inspected, and <br />dates serviced, if any. This record shall be available for <br />inspection by the fire marshal. <br />5 Subsection 38„~1 d Stan_,_~_ <br />~ } ~~_..~.__~.,.~~.,.__,_dards, fi s hereby amended by deleting <br />the words "UBC Standards Nos. 38-1, 38-2, and 38-3" including the same word- <br />ing as appears fin exception number one and replacing in both locations the <br />wards "Standard for the Installation of Sprinkler systems, NFPA 13, 1978 <br />Edition, as adopted and copyrighted by the National Fire Protection Associ- <br />ati on . " <br />~5} Section 38D2 b , there Re uired is hereb amended b addi <br />y y ng <br />subparts E. and F. to Subdivision 1. entitled, All occupancies, except Group <br />R, Division 3, Group M, to read: <br />E. In every existing or new building or structure which has <br />no access to a public street except by way of a pedestrian mall <br />or to which access by f i re~-f i ghtfi ng equipment i s restricted by one <br />or more structures or amenities in the public street or right-af- <br />way, the requirements to apply one year after construction of the <br />building or the making of a restriction, whichever time is the <br />later; provided, however, the area and height increases specified <br />