Laserfiche WebLink
ment connection and a swing check valve on the sup ly <br />side. p <br />EXCEPTION: The fire department connection may <br />be omitted when the water supply to the buildin is <br />ca ab1 a of s i g <br />p mul taneously operating the number of <br />sprinkler heads installed in the two largest se cr- <br />ate areas which p <br />are directly ~ntercannected by a <br />normally closed door, or when waived by the chief <br />or his/her designee. <br />~} Basements: Where automatic sprinklers are re wired to <br />protect onl basements and ~ q <br />y~ where na other part~on of the bu~ld~ng <br />~s to be equipped with automatic sprinklers, water su lies ma <br />be served throw h the fo pp y <br />g llow~ng arrangements: <br />1. if the basement is 10,000 square feet or less in <br />area, water service may be supplied by a twa-inch I,D. i e, <br />Z. If the basement ' p p <br />~s less than 10,000 square feet but <br />more than 5,000 square feet in area, at least one 2-1 2 inch <br />two-way s~amese fire department connection placed on the <br />street front of the building in an unobstructed ositi0n at <br />1 east one foot and p <br />not mare than four feet above the adjacent <br />ground level shall be provided and connected to the main <br />sprinkler system supply by means of Z-1/2 inch I,D. i e. <br />3. If the basem p P <br />ent ~s 5,000 square feet or less in area, <br />at least one 2-1/2 inch fire department connection mounted <br />not less than one foot and not more than four feet above the <br />adjacent ground level shall be provided and connected to the <br />main sprinkler system supply by means of a 2-1/2 inch I.D, <br />pipe. <br />4. Basements exceeding 10,000 square feet in area sha11 <br />be served by standard water supplies as rescribed in U.B.C. <br />Standard Nv. ~ ~ p <br />38 1, or shall be subd~v~ded into sections not <br />exceeding 10,000 square feet by one-hour fire-resistive occu- <br />pancy separations. <br />~j}. Limited Access Structures. Standard automatic fire - <br />t~ ngu~ shy n s stems shat 1 ex <br />9 Y be i nsta~ 1 ed and maintained i n an exi st- <br />~ng or new building which has no access to a public street exce t <br />by way of a edestrian mall ar ~ ~ p <br />p to which access by fire fighting <br />equipment is restricted by one or more structures or amenities in <br />a public street or right-of-way, the requirement to a 1 ane <br />after construction of t ~ ~ pp y .year <br />e , he budding or the make ng of the restr~ c- <br />t~on, whichever time is later. <br />~k} Fire Extin uishin S stem in Hi h-Rise Structures. <br />1. Every structure five or more stories ar rester than <br />45 feet in hei ht •g <br />g , shall have an approved automatic fire ext~n- <br />gu~sh~ng system installed throughout, includin the basement. <br />The number of s g <br />tor~es ar height of the structure shall be <br />measured f ram the lowest 1 evel of fire department veh i cl e <br />access, <br />2. The provisions of subsection 1. of this section sha11 <br />not apply to existing structures other than Grou R Occu an- <br />p p <br />cies so long as: <br />a. The existing structure does not constitute a <br />life ar safety hazard to its occupants; ar <br />Ordinance - 10 <br />