Laserfiche WebLink
Table 50.306-E <br />STORAGE OF CLASS 1 OXIDIZERS IN COMBUSTIBLE CONTAINERS (FN 1) <br />Piles <br />fnnrl i t i nn <br />Pi1p I imitc <br />Length Meet} Na Limit <br />Width Meet} 50 <br />Height Meet} 2D <br />Distance to next pi ] e Meet} 3 <br />Distance to wa11 s Meet} 2 <br />Maximum Quantity per Building Na Limit <br />FN I. Starage in noncombustible containers or in bulk in <br />detached storage buildings is not limited as to <br />quantity or arrangement. <br />Table 80.306-F <br />STORAGE OF CLASS 2 OXIDIZERS IN COMBUSTIBLE CONTAINER5 FN 1 2 3 <br />Segregated <br />Condition AS Cutoff Detached <br />Piles <br />Height Meet} lQ 12 I2 <br />Distance to next <br />Pi 1 e Meet} -- FN 2 FN 2 <br />Distance to walls <br />Meet} ~ 2 2 <br />Maximum Quantity per <br />Pile Tons} 20 50 200 <br />Maximum Quantity per <br />Building Tons} 200 500 No Limit <br />FN 1. Storage in noncombustible containers is not limited as <br />to quantity or arrangement, except that piles shall be <br />at least two feet from walls in nansprinklered buildings <br />and four feet from walls in sprinklered buildings; dis- <br />tance between piles shall be not less than the pile <br />height. <br />FN 2. Aisle width shall be not less than the pile height. <br />FN 3. Quantity limits shall be reduced by 50% in buildings <br />or pardons of buildings used for retail sales, <br />Table 80,306-G <br />STORAGE OF CLASS 3 OXIDIZERS IN CONTAINERS FN I,2 <br />Condition Se re ated Cutoff Detached <br />r~ies <br />Height (feet) 8 10 10 <br />Distance to next <br />Pile (feet} FN 3 FN 3 FN 3 <br />Distance to walls <br />(feet) 4 4 4 <br />Maximum Quantity per <br />Pile (Tons) 20 30 150 <br />Ordinance - 42 <br />